Refrigerant compatibility guide

A starting point, not an authority. The equipment nameplate is the only thing that decides what goes into a system — this page just helps you narrow it down before you walk to the truck.

Read this first

No refrigerant on this site is a universal drop-in. Substituting one for another without a manufacturer-approved, model-specific retrofit procedure voids equipment warranties, can destroy a compressor, and in the case of putting an A2L into a system not rated for it, creates a genuine fire risk. Mixing two refrigerants in one circuit makes the charge unrecoverable and unusable.

Quick lookup

By equipment type.

EquipmentUsually takesNotesClass
Residential split A/C, installed 2023+R-454B or R-32Check the plate — manufacturers split between the two.A2L
Residential split A/C, 2005 – 2023R-410AThe dominant charge of that era. High pressure — rate your gauges.A1
Residential split A/C, pre-2005R-22 (reclaimed)Virgin production ended in 2020. Reclaimed only, or plan a replacement.A1
Ductless mini-split / VRF, recentR-32 or R-454BCommon on inverter equipment. Verify per indoor and outdoor unit.A2L
Heat pump, air sourcePer nameplateR-410A on the installed base, R-454B or R-32 on new equipment.Varies
Walk-in freezer, low temperatureR-404A or R-448AR-448A is the lower-GWP path for both new builds and conversions.A1
Supermarket rack, medium temperatureR-448AStandard R-404A replacement. Runs hotter — check compressor limits.A1
Display case / reach-in coolerR-134a or R-448ADepends on age and design temperature. Read the plate.A1
R-22 retrofit, air conditioningR-407CRequires an oil change to POE and a manufacturer-approved procedure.A1
Automotive A/C, pre-2015 vehiclesR-134aSection 609 certification. PAG oil, never POE.A1
Automotive A/C, 2015+ vehiclesR-1234yfNot stocked. Check the underhood label before ordering anything.A2L
Centrifugal chiller, comfort coolingR-134aConfirm against the chiller nameplate and the manufacturer service manual.A1
Side by side

The full comparison.

Everything we stock, with the numbers that actually change how you service the system.

RefrigerantTypeClassGWPGlideLubricantNet wt
R-454BHFO / HFC blend A2L 466≈ 0.2 °F · near-azeotropicPOE (polyol ester)22 lb View
R-410AHFC blend A1 2088< 0.3 °F · near-azeotropicPOE (polyol ester)25 lb View
R-32HFC, pure compound A2L 675None · single componentPOE (polyol ester)20.9 lb View
R-22HCFC, pure compound A1 1810None · single componentMineral oil or alkylbenzene30 lb View
R-407CHFC zeotropic blend A1 1774≈ 13 °F · high glidePOE (polyol ester)25 lb View
R-404AHFC near-azeotropic blend A1 3922≈ 0.9 °F · near-azeotropicPOE (polyol ester)24 lb View
R-448AHFO / HFC zeotropic blend A1 1387≈ 9 °F · moderate glidePOE (polyol ester)25 lb View
R-134aHFC, pure compound A1 1430None · single componentPAG (mobile A/C) · POE (stationary)30 lb View
Working knowledge

Four things that trip people up.

Glide changes how you read pressures

A zeotropic blend like R-407C (≈13 °F) or R-448A (≈9 °F) boils and condenses across a temperature range, not at a single point. Use bubble point for subcooling and dew point for superheat. Reading a single-value P-T chart on a high-glide blend will send you chasing a fault that is not there.

Charge blends as liquid

Pull from the cylinder in the liquid phase — inverted, or from a dip-tube cylinder — and meter it in. Charging a blend as vapour lets the lighter components leave first, so the cylinder and the system both end up with the wrong composition. Pure compounds like R-32, R-134a and R-22 are exempt from this.

The oil has to match

POE for HFC and HFO blends, mineral oil or alkylbenzene for R-22, PAG for mobile R-134a systems. POE is hygroscopic — it pulls moisture out of the air fast, so keep containers capped and pull a proper vacuum. Most “refrigerant problems” that end in a compressor failure were oil problems.

A2L is a tooling decision, not just a gas

R-32 and R-454B are mildly flammable. They need flammable-rated recovery machines, gauges, vacuum pumps and leak detection, plus ventilation and ignition-source control at the work area. Sort the tools before the cylinder shows up, not after.

Still not sure?

Send us the equipment make, model and nameplate photo and we will tell you what it takes — including when the answer is “nothing we sell”. Call +1 (888) 742-0164 or send a message.

Factory sealed

New, unused cylinders with intact valve seals and legible labels.

Compliant sales

Section 608 / 609 credentials verified before any cylinder ships.

Free FedEx ground

Hazmat-certified packaging, no freight surcharge, no minimum order.

Out in 24 hours

Orders placed before 2 PM CST leave the dock the same business day.

Refrigerants are sold for professional service use only. Purchases of HFC and HCFC refrigerant for stationary equipment require EPA Section 608 technician certification or a qualifying exemption; motor-vehicle air-conditioning refrigerant requires Section 609 certification. RefrigiMart verifies credentials before shipment. Always follow the equipment nameplate, the safety data sheet and all federal, state and local requirements. Product specifications are published reference values and do not replace the manufacturer's documentation.